ETL 1110-3-498
24 Feb 99
G-4. Building Number 2.
Building number 2 is a poured concrete structure with 0.66-m-thick walls and roof. The facility
has no windows. Leakage rate versus internal pressure is shown in Figure G-2. Building leakage
rates can be calculated using equation G-2.
log(y) = C0 + C1log(x)
(eq G-2)
where: C0 = 1.8871234
C1 = 0.54579516
y = leakage rate, L/s
x = internal pressure, Pa
10,000
Wall Type 5: 6600 mm (26") thick, with 8 mm (1/4") Spall Plate
Roof Type 3: 6600 mm (26") Thick
1,000
100
10
1
10
100
1,000
Internal Pressure, Pa
Figure G-2. Building 2 Leakage Rate.
G-4