ETL 1110-2-560
30 Jun 01
where
λ′ = adjusted failure rate - failures/year
t′ = adjusted time variable (operation time) - years
E-4. Results
The results for the electrical subsystems are shown in spreadsheet format in Tables E-3 through E-7. It is
evident that the lock electrical distribution reliability is much less than that of any other electrical subsys-
tem evaluated. This was attributed to the 100 percent demand on the major components of that subsystem
and also its greater failure rate.
Table E-1
Failure Rate Data of Electrical Components from ANSI/IEEE (1980)
Failure Rate
6
Component (Failures per Unit-Year)
per 10 Experience Hours
Electric Utility Power Supplies, Single Circuit (0.537)
61.3014
Liquid Filled, All (0.0041)
0.4680
Dry-Type (0.0036)
0.4110
7.6500
E-6